Building sewer fixture load estimator: will one service carry the whole building?

Tally fixture units for every unit and suite in a multiplex, find the smallest building sewer the code allows, and test the existing service against it.

Conceptual illustration of whole-building fixture rows feed a separate pipe-size review board
Illustrated field guideWhole-building fixture rows feed a separate pipe-size review boardUnits · suites · fixtures · slope · existing service
Short answer

This estimator adds up the hydraulic load of a whole building, unit by unit and suite by suite, using the fixture-unit values in the National Plumbing Code of Canada 2020. It then finds the smallest building sewer the code table permits at your slope and compares the total with the size and slope of the service already in the ground.

Key takeaways
  • Load is counted in fixture units from NPC Table 2.4.9.3: a bathroom group with a tank toilet is 6, a kitchen sink 1.5, a clothes washer 2.
  • Capacity comes from NPC Table 2.4.10.6.-C: a 4-inch building sewer carries 180 fixture units at 1 in 100 and 240 at 1 in 50.
  • A building sewer to a public sewer must be at least NPS 4 downstream of the main cleanout, so a 3-inch service is flagged whatever the load.
  • Passing the fixture-unit test does not mean the city will let an old service stay; condition, material and local rules decide that.
  • Ontario applies its own Building Code, and many cities set larger minimum service sizes than the plumbing code.
Free tool · runs in your browser

Building Sewer Fixture Load Estimator

Whole-building fixture units for six example buildings against building sewer capacityHorizontal bars show hydraulic load in fixture units for six example buildings: a single house at 23.5, a house with a secondary suite at 33, a duplex at 47, a fourplex at 68, a sixplex at 99 and four units with four suites at 112. Vertical lines mark National Plumbing Code capacities for a 4-inch building sewer: 180 fixture units at 1 in 100 and 240 at 1 in 50. The fixture mixes are illustrative; count your own drawings. Single house23.5 FUHouse + suite33 FUDuplex47 FUFourplex68 FUSixplex99 FU4 units + 4 suites112 FU NPS 4 AT 1 IN 100180 FUNPS 4 AT 1 IN 50240 FU WHOLE-BUILDING LOAD, FIXTURE UNITS (NPC TABLE 2.4.9.3) · EXAMPLE MIXES, ILLUSTRATIVE At this scale, condition and city rules decide more often than pipe size.
Fig. 1Whole-building hydraulic load climbs as a lot densifies, but a 4-inch building sewer at 1 in 100 is rated for 180 fixture units. The example fixture mixes are illustrative; the capacities are NPC 2020 Table 2.4.10.6.-C.

01 /What does the fixture load estimator do?

It answers the sizing question that comes up the moment a lot is densified: once the house becomes a house with a suite, a duplex or a fourplex, how much drainage load reaches the building sewer, what size of pipe does the plumbing code call for, and can the service already in the ground take it? Most calculators size one pipe from a short list of fixtures. This one is built around dwelling units, so you describe a typical unit and a typical suite, say how many of each there are, add the building-wide items, and read the result for the whole building.

Every number the widget uses is published in the National Plumbing Code of Canada 2020 (second printing, with the February 2025 errata), which this site fetched and read in September 2026. Nothing is estimated from rules of thumb. Where the code is silent, for example on whether a city will accept a sixty-year-old clay service, the tool says so and points you to the city.

Whole-building fixture units for six example buildings against building sewer capacityHorizontal bars show hydraulic load in fixture units for six example buildings: a single house at 23.5, a house with a secondary suite at 33, a duplex at 47, a fourplex at 68, a sixplex at 99 and four units with four suites at 112. Vertical lines mark National Plumbing Code capacities for a 4-inch building sewer: 180 fixture units at 1 in 100 and 240 at 1 in 50. The fixture mixes are illustrative; count your own drawings. Single house23.5 FUHouse + suite33 FUDuplex47 FUFourplex68 FUSixplex99 FU4 units + 4 suites112 FU NPS 4 AT 1 IN 100180 FUNPS 4 AT 1 IN 50240 FU WHOLE-BUILDING LOAD, FIXTURE UNITS (NPC TABLE 2.4.9.3) · EXAMPLE MIXES, ILLUSTRATIVE At this scale, condition and city rules decide more often than pipe size.
Fig. 2Six example buildings and their whole-building load in fixture units, against the two NPC capacities for a 4-inch building sewer. The mixes match the tool's presets.

02 /Which inputs does it ask for?

The form has four groups. Start from a preset and adjust, or choose Custom to keep your own numbers when you change the building type.

Inputs and what each one changes
InputChoicesWhat it changes
Start from a buildingSingle house, house with a suite, duplex, triplex, fourplex, sixplex, four units with four suites, customResets every fixture count to the preset: unit and suite counts, NPS 3 floor drains, and a powder room per unit for the house, suite and duplex presets
Main dwelling units and secondary suites0 to 40 eachMultiplies the per-unit and per-suite fixture totals
What the sewer will serveOne building; one building plus a suite building on the same lot; two or more principal buildingsAdds the separate-service notes from NPC 2.1.2.4
Fixtures in each main unit and each suiteCounts of eight fixture typesSets fixture units per unit and per suite
Building-wide itemsNPS 3 and NPS 2 floor drains, pumped flow in L/s, roughed-in or future fixture unitsAdded once to the total
New building sewer slope1 in 200, 1 in 133, 1 in 100, 1 in 50, 1 in 25Chooses the column of the capacity table
City minimum sizeNone stated, 100 mm, 125 mm, 150 mmRaises the recommendation if the city asks for more
Existing service size, slope and conditionNone, 3, 4, 5 or 6 inch; slope known or not; four condition statesDrives the existing-service verdict and notes

The eight fixture types, with their fixture-unit values from Table 2.4.9.3, are: a bathroom group of a tank toilet, basin and tub or shower (6); an extra tank toilet (4); an extra basin (1); a domestic kitchen sink with or without a food waste grinder (1.5); a domestic clothes washer (2); a separate shower whose heads together discharge under 9.5 L/min (1.5); a separate bathtub (1.5); and a laundry tray (1.5). Floor drains carry 3 fixture units with an NPS 3 trap and 2 with an NPS 2 trap.

03 /How does it add up the load?

The total is the per-unit fixture sum times the number of main units, plus the per-suite sum times the number of suites, plus floor drains, plus pumped flow, plus any provision for future fixtures. That follows Article 2.4.10.1, which defines the load on a pipe as every fixture connected upstream plus every fixture for which provision is made for a future connection. The result table shows each part so you can see where the load comes from.

  1. Per unit

    Each fixture count times its fixture-unit value, summed. The fourplex preset uses two bathroom groups, a kitchen sink and a clothes washer: 12 + 1.5 + 2 = 15.5 FU per unit.

  2. Per suite

    The same for a typical suite. The default suite is one bathroom group, a kitchen sink and a washer: 9.5 FU.

  3. Building items

    Floor drains at 3 or 2 FU each. A pump or ejector that discharges into the sewer counts as a continuous flow at 31.7 FU for each litre per second, from Sentence 2.4.10.3.(1).

  4. Future provision

    Any roughed-in fixtures you enter, in fixture units, because the code counts provision for future connection now.

  5. Total

    The fourplex preset gives 4 × 15.5 + 2 × 3 = 68 FU. Four units with four suites and four floor drains gives 112 FU.

04 /How does it choose a pipe size?

It walks up Table 2.4.10.6.-C at the slope you chose and returns the smallest size from NPS 4 upward whose tabulated capacity is at least the total. NPS 3 is never recommended for the building sewer, because Article 2.4.9.4 requires building drains and sewers connected to the public system downstream of the main cleanout to be at least NPS 4. If the table lists no capacity for a size at that slope, the size is skipped: a 4-inch pipe has no entry flatter than 1 in 100, and 5 and 6 inch pipes none flatter than 1 in 133.

Building sewer capacity in fixture units by pipe size and slopeA grid from National Plumbing Code of Canada 2020 Table 2.4.10.6.-C. Rows are pipe sizes NPS 3, 4, 5, 6 and 8; columns are slopes from 1 in 200 to 1 in 25. A 3-inch pipe carries 27 fixture units at 1 in 50 and 36 at 1 in 25. A 4-inch pipe carries 180 at 1 in 100, 240 at 1 in 50 and 300 at 1 in 25. A 5-inch pipe carries 380 to 670, a 6-inch pipe 600 to 1,300, and an 8-inch pipe 1,400 to 3,370. Dashes mean the size is not permitted at that slope. 1 in 2001 in 1331 in 1001 in 501 in 25 SIZE NPS 3———2736NPS 4——180240300NPS 5—380390480670NPS 6—6007008401,300NPS 81,4001,5001,6002,2503,370 MAX. LOAD IN FIXTURE UNITS · NPC 2020 TABLE 2.4.10.6.-C · SANITARY BUILDING SEWER STEEPER → MORE CAPACITY To a public sewer: at least NPS 4 downstream of the main cleanout (2.4.9.4).Many cities set a larger minimum for multi-unit services. Ask yours.
Fig. 3The capacity table the estimator reads. It picks the column for your slope and the first row that carries your total.

If you enter a city minimum larger than the code result, the widget shows both and treats the larger as the size to plan around. That matters more than it sounds: Toronto's online process for buildings of up to 5 units is built around a 150 mm sewer connection, and older Ottawa infill specifications show a 125 mm sanitary service. The code number is the floor, not the answer. If the load exceeds what NPS 12 carries at your slope, the tool says the building needs an engineered design.

05 /How does it judge the existing service?

The existing-service check is a paper test of size and slope, followed by honest notes about everything paper cannot tell you.

  • 3 inch: flagged as too small for a building sewer to a public sewer under 2.4.9.4, whatever the load.
  • Size and slope known: the load is compared with the table capacity at that slope and shown as a percentage. If the slope is flatter than the flattest permitted for that size, the table gives no capacity and the pipe is flagged.
  • Slope unknown: the tool uses the flattest slope the table permits for that size, which is the most cautious assumption, and asks you to measure the inverts.
  • Smaller than your city minimum: flagged, whatever the load.
  • Condition: unknown, defects on camera, or clay, fibre or cast iron not yet filmed each add a note. A sound pipe on recent video is the only case where the verdict says the load fits without a condition warning.

Many cities decide reuse on grounds the plumbing code does not cover. On a demolish-and-rebuild, Calgary's design guidelines call for new water, sanitary and storm services; Toronto and Vancouver accept reuse only for PVC in good condition with a video; Halifax Water requires replacement at the owner's cost when a service 30 years or older serves a redevelopment. Our guide to reusing an existing sewer service sets these out city by city.

Four questions before reusing an existing sewer serviceAn existing service runs from an old house footprint to the main. Four questions are stacked beside it. First, does the city allow it to stay on a redevelopment? Second, what is it made of and what condition is it in, based on a camera video? Third, is it big enough for the new fixture-unit load at its slope? Fourth, does its depth and position suit the new foundation? A no to any of them usually means a new service, and the old one is abandoned the way the city specifies. OLD HOUSE(to be removed) EXISTING SERVICE MAIN 1ALLOWED TO STAY?some cities require a newservice on redevelopment2MATERIAL + CONDITIONcamera video, age, clay,fibre, cast iron, defects3BIG ENOUGH?new fixture-unit load vssize and slope (NPC table)4IN THE RIGHT PLACE?depth and position suitthe new foundation ANY "NO" → A NEW SERVICE; THE OLD ONE IS ABANDONED AS THE CITY SAYS DECISION AID · ILLUSTRATIVE · THE MUNICIPALITY DECIDES REUSE CAN THE OLD SERVICE TAKE THE NEW BUILDING?
Fig. 4The four questions behind the existing-service verdict. The tool answers the third on paper; the city answers the first.

06 /What do the separate-building and suite notes mean?

If you say the sewer serves one building plus a suite building on the same lot, the tool keeps the suite's fixtures in the total and reminds you of two code points. Article 2.1.2.4 lets an ancillary building on the same property share the service, and Sentence 2.4.7.2.(4) limits the developed length between a building and the building sewer it joins, other than at a manhole, to 30 m. If you say the sewer serves two or more principal buildings, it tells you to run the estimate per building, because each building connected to public services must be connected separately.

Whenever suites are present, the tool also notes that a normally open backwater valve in a building drain may serve only one dwelling unit (Sentence 2.4.6.4.(5)). That rule does not change the fixture count, but it changes the drain layout below the street level, which is covered in the secondary suite plumbing guide.

07 /What are the limits of this estimate?

  • It sizes the sanitary building sewer only. Storm and combined building sewers are sized by rainfall load under a different table (2.4.10.9), and water services by a different method.
  • It assumes the fixtures listed. Commercial kitchens, flush-valve toilets, large showers over 9.5 L/min and other fixtures carry different values; add them as future fixture units if you know their load.
  • It reads the National Plumbing Code 2020. Alberta has had it in force since April 1, 2023. Ontario uses the Ontario Building Code, and Vancouver has its own Building By-law, so the governing table may differ slightly: confirm with the permit office.
  • It cannot see the pipe. Roots, offsets, sags and belly sections reduce real capacity, which is why the verdict defers to a camera run.
  • It does not decide anything. The designer, the permit office and the utility do.

When the numbers are in, take them to the Service Connection Planner to see what your city asks for, read how building sewers are sized for the reasoning, or ask for quotes with your fixture total in hand.

FAQQuestions people ask

How many fixture units can a 4 inch building sewer take?

Under National Plumbing Code 2020 Table 2.4.10.6.-C, a 4-inch sanitary building sewer carries up to 180 fixture units at 1 in 100, 240 at 1 in 50 and 300 at 1 in 25. It is not permitted flatter than 1 in 100.

How many fixture units is a fourplex?

It depends on the fixtures. With two full bathrooms, a kitchen sink and a washer per unit and two floor drains, a fourplex totals 68 fixture units, well inside a 4-inch sewer at 1 in 100. Enter your own plan to check.

Does a secondary suite need a bigger sewer line?

Rarely because of fixture units alone: a typical suite adds about 9.5 fixture units. The size question is usually settled by the city's minimum and the condition of the existing pipe, not by the load.

Do I count the dishwasher in the fixture load?

Not if it drains through the kitchen sink or its food waste grinder; the code assigns it no separate load in that case. A dishwasher with its own trap and outlet carries 1.5 fixture units.

How are sump or ejector pumps counted in fixture units?

A pump that discharges continuously into a sanitary drain counts as 31.7 fixture units for each litre per second of flow, under Sentence 2.4.10.3.(1). Enter the pump's design flow in the pumped-flow box.

Why does the tool never recommend a 3 inch building sewer?

Because Article 2.4.9.4 requires building drains and sewers connected to the public system downstream of the main cleanout to be at least NPS 4, whatever the load.

NETWORKGo deeper across the HAUSE Sewer network

Request quotes

Describe the problem once. Get a straight answer.

Send the symptoms and anything you already know — age of the house, what a camera found, what you have been quoted. The HAUSE Sewer desk replies with next steps and, where available, a local contractor for the job.

Sewage backing up right now? Stop using water, keep people away from the water, and do not touch electrical equipment near it.